Content-Type: text/html; charset=UTF-8
Michael,
Other Portions of the Buildi=
ng pertains to the distance between the stairs and other portions of=
the same building. This is to prevent fire from easily spreading from one =
part of the building to another.
The phrase “For the purposes=
of this section, other portions of the building shall be treated as separa=
te buildings” means that, when applying the regulations mentioned in=
this section (1027.5), the different parts or sections of the building are=
considered and treated as if they were individual, standalone buildings. T=
his treatment is done specifically for the purpose of determining and confo=
rming compliance with the fire separation requirements outlined in section 1023.2 (as described in section 1027=
=2E6)
1027.6 Exterior exit stairways and ramps shall be separated from the int=
erior of the building as required in Section 1023.2 (fire barrier.)
In other words, when assessing whether the exterior exit stairways and r=
amps meet the specified fire separation distances from adjacent lot lines, =
other parts of the building, and other buildings on the same lot, each port=
ion of the building is treated as if it were its own separate building. Thi=
s approach ensures that adequate fire safety measures are taken within the =
building itself and in relation to neighboring properties.
By treating different sections of the building as separate buildings for=
the purposes of this regulation, the intention is to prevent fire from eas=
ily spreading between different parts of the same building, as if they were=
entirely distinct structures. This helps to contain the potential impact o=
f a fire and enhance the overall fire safety of the building and its surrou=
ndings.
A one-hour separation shall =
suffice for and substitute the 10-feet minimum distance required by section=
1027.5.
Please, let me know if additional clarifications are needed.
Thanks!
Allen Haidar,
EJD, AIA, LEED AP
H & H Codes
Architec=
ts | General Building Contractors
ADA | Building Envelope | TPR
(626) 358-1111 * (808) 745-3656
www.hhcodes.com
IMPORTANT-CONFIDENTIAL:
This message and any atta=
chments are intended only for the use of the individual or entity to which =
it is addressed, and may contain information that is privileged, confidenti=
al, and/or exempt from disclosure under applicable law.
On 2023-08-15 09:43, Michael Riehm wrote:
bsp;
27.5 Location. Exterior exit stairways and ramps shall have a minimum fire separation=
distance of 10 feet (3048 mm) measured at right angles from the exterior e=
dge of the stairway or ramps, including landings, to:
Adjacent lot lines.
Other p=
ortions of the building.
Other buildings on the same lot unless =
the adjacent building exterior walls and openings are protected in accordance with Section 705 based =
on fire separation distance.
Fo=
r the purposes of this section, other portions of the building shall be tre=
ated as separate buildings.
Mobile: 808-936-8202
Email: mjriehm001@gmail.com